Aisle between rows of modular drawer panels in a shop
MCCs with drawer units being assembled at Auti.

In the electrical room of almost every plant, the main low-voltage switchboard and the MCC stand side by side, and each has its own job. The main LV switchboard is where power comes in: it takes the supply from the transformer and distributes it, already protected, to the rest of the plant. The MCC, or Motor Control Center, takes care of the motors: it starts, protects and controls every pump, conveyor and fan in your plant.

At Auti, we design, build and test both to order, following IEC 61439 (NBR IEC 61439 in Brazil). Before the panel ships to site, you attend the factory acceptance test (FAT) and see everything working. In this article, we explain how the two differ, what has to be defined before manufacturing and what to send to get an accurate quote.

How does an MCC differ from a main LV switchboard and a control panel?

Think about the path power takes through the plant. It comes from the transformer into the main LV switchboard, which distributes and protects the main circuits. From there, one of the feeders goes to the MCC, where the motor starters are. The control panel handles the logic: the PLC decides when each motor starts and stops.

In small plants, these functions sometimes share a single panel. In larger plants, keeping them apart makes maintenance and temperature control easier.

Main LV switchboardMCCControl panel
PurposeDistribute and protect the plant's powerStart, protect and control motorsRun the control logic
What's insideMain breaker, busbars, feeders, meteringDirect-on-line starters, soft starters, drives, motor circuit breakers, contactorsPLC, I/O cards, HMI, power supplies, interface relays
Where power comes fromTransformer or LV incomerFeeder from the main LV switchboardControl circuit

What has to be defined before manufacturing

To put together a quote, we need this information:

  • Busbar current and short-circuit current (kA) at the point where the panel will be installed.
  • Motor list, with the power, voltage and starting method of each motor: direct-on-line, star-delta, soft starter or drive.
  • Fixed or withdrawable units. Withdrawable drawers let you replace a circuit without shutting down the whole panel, but they cost more.
  • Form of internal separation (Forms 1 to 4 under IEC 61439-2), which defines what is segregated from what inside the panel.
  • Environment: degree of protection (IP), ventilation, dust, humidity, temperature and salt-laden air.
  • Space and cables: where cables enter and leave (top or bottom), the space available in the room and spare capacity for growth.
  • Communication with the automation system: hard-wired or networked signals (Profinet, EtherNet/IP, Modbus) and the point list.

If you do not have some of this data yet, our engineering team can visit your plant and carry out a site survey for the quote.

Where we have built MCCs and panels

Four Siemens SIRIUS soft starters side by side with clear terminal covers
Siemens SIRIUS soft starters in a motor starter panel.

Auti has worked in electrification, industrial automation and electrical panels for 20 years. In that time, our MCCs and switchboards have gone into very different plants, and most of our experience is in four sectors:

  • Paper: more than 40 paper machines run with equipment supplied by Auti. The scope ranges from MCCs, switchboards and automation panels to control logic, SCADA systems and DCS, plus commissioning and start-up. One of them is a tissue machine with one of the largest Yankee dryers in Brazil.
  • Ports: many plants in port areas, with a strong presence at the Port of Paranaguá, including one of the large grain receiving pits. At these terminals, we supply the MCCs and the automation and bring our own team for commissioning and start-up.
  • Agribusiness: many projects with MCCs and automation.
  • Wood: the wood yard of a wood-based panel manufacturer, where we delivered the automation, the electrical panels and the electrical infrastructure.

Each of these plants demands something different from the panel. At the port, it lives with grain dust and salt air. At the paper mill, with heat and humidity. That is why the environment is on the list of things to define before manufacturing.

How the panel is tested before it leaves the factory

IEC 61439 requires two different verifications. The first, design verification, proves that the panel design withstands the rated current, short-circuit and temperature rise. It can be done by test, by calculation or by design rules. The second, routine verification, is carried out on every panel that leaves the factory: inspection, wiring, insulation and operation.

Then comes the FAT. This is when you, or someone from your team, see the panel working before it ships: checking the assembly, the controls, the interlocks and the communication with the automation system. The FAT does not replace site commissioning. After transport and installation, the panel is tested again, this time connected to the loads.

How the MCC talks to the PLC

An MCC with communication reports the status, current, alarms and faults of each motor to the automation system. For this to work, the signal list and the network architecture must be defined together with the electrical design, not afterwards. Because Auti also programs PLCs and SCADA systems, we can deliver the MCC and the integration under the same contract, with a single party responsible.

Who builds MCCs and main LV switchboards in Brazil?

There are two routes. Electrical equipment manufacturers have their own MCC and switchboard product lines. Panel builders and system integrators, such as Auti, design and build the assembly to suit your plant, often using systems certified by those manufacturers.

Whichever route you take, ask the supplier two things: how they prove design verification under IEC 61439, and whether they are certified by the manufacturer of the system they will use.

Auti is based in São José dos Pinhais, in the state of Paraná, serves all of Brazil and Latin America, and holds these certifications:

SIVACON S4Certified developer of the Siemens low-voltage switchboard system, in line with IEC 61439.
Siemens panel buildersListed among Siemens low-voltage panel builders.
Siemens Solution PartnerDrives & Motion, Factory Automation, Industrial Communications and PCS 7.
Rockwell AutomationSilver System Integrator, including Low Voltage Drives.
ABBValue Provider for power and automation equipment.
See the certificates in Partners and Certifications

What to send for a quote

With these documents, we can send back a technical proposal without back-and-forth:

  1. Single-line diagram.
  2. List of motors and loads, with power, voltage and starting method.
  3. Short-circuit current at the installation point.
  4. Plant technical specification and accepted brands.
  5. Fixed or withdrawable units and form of separation, if already defined.
  6. Communication protocol and signal list for the automation system.
  7. Installation site, available space and required lead time.

Frequently asked questions

What is the difference between an MCC and a main LV switchboard?

The MCC takes care of the motors: it starts, protects and controls each one. The main LV switchboard distributes and protects power for the whole installation and usually feeds the MCCs.

Does every MCC need withdrawable drawers?

No. Withdrawable drawers pay off when the plant cannot stop to replace a circuit. Otherwise, fixed units do the job and cost less.

What is a form of separation?

It is the level of internal segregation between busbars, functional units and terminals, defined as Forms 1 to 4 in IEC 61439-2. The higher the form, the easier it is to work on one part while the others stay live.

If the panel passed the FAT, can it be energized?

Not yet. The FAT validates the panel at the factory. After transport and installation, site commissioning tests the interconnections and the loads before start-up.

Does Auti build MCCs and switchboards to IEC 61439?

Yes. We build low-voltage panels to NBR IEC 61439, we are a certified developer of the Siemens SIVACON S4 system and we carry out a FAT before every delivery.

Does Auti serve plants outside Paraná?

Yes. We serve all of Brazil and Latin America.

Have an MCC or switchboard to quote?

Send the single-line diagram and the motor list to our technical team.

Request a proposal